3.1.5.19. Combustible Piping Materials

Articles need to know!!!


3.1.5.19. Combustible Piping Materials

1) Except as permitted by Clause 3.1.5.2.(1)(d) and Sentence (2) and (3), combustible piping and tubing and associated adhesives are permitted to be used in a building required to be of noncombustible construction provided that, except when concealed in a wall or concrete floor slab, they

a) have a flame-spread rating not more than 25, and

b) if used in a building described in Section 3.2.6., have a smoke developed classification not more than 50.