3.1.10.7. Combustible Projections

Articles need to know!!! #firewall


3.1.10.7. Combustible Projections

1) combustible material shall not extend across the end of a firewall but it is permitted to extend across a roof above a firewall that is terminated in conformance with Sentence 3.1.10.3.(2).

2) If buildings are separated by a firewall, combustible projections on the exterior of one building, including balconies, platforms, canopies, eave projections and stairs, that extend outward beyond the end of the firewall, shall not be permitted within 2.4 m of combustible projections and window or door openings of the adjacent building.