3.1.8.7. Location of Fire Dampers and Smoke Dampers

 Articles need to know!!!


3.1.8.7. Location of Fire Dampers and Smoke Dampers


1) Except as provided in Article 3.1.8.8., a fire damp having a fire protection rating conforming to Sentence 3.1.8.4.(2) shall be installed in conformance with Article 3.1.8.10. in ducts or air-transfer openings that penetrate an assembly required to be a fire separation.


2) Except as provided in Article 3.1.8.9., a smoke damper or a combination smoke/fire damper shall be installed in conformance with Article 3.1.8.11. in ducts or air-transfer openings that penetrate an assembly required to be a fire separation, where the fire separation

a) separates a public corridor,

b) contains an egress door refereed to in Sentence 3.4.2.4.(2)

c) serves an assembly, care, treatment, detention or residential occupancy, or

d) is installed to meet the requirements of Clause 3.3.1.7.(1)(b) or Sentence 3.3.3.5.(4).